Step 1 of 14
Download and install the iCONNECT app

Install the app on your mobile device, launch it and grant all required permissions (Bluetooth, location).

Step 2 of 14
Log in to your iCONNECT account

Register or log in to your iCONNECT account in the app.

💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 3 of 14
Enable Bluetooth communication

Switch the heat recovery unit control panel from Wi-Fi to Bluetooth.

For iSWITCH Ti: press and hold the [on/off] icon on/off until all panel indicators begin flashing. Rapid flashing (several times per second) = Bluetooth active.
For iSENSE 5i: on the home screen tap: User Menu Settings Wi-Fi Mode — switch from WiFi to BT Letters BT in the top bar = Bluetooth active.
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 4 of 14
Search for the unit in the app

Connect to the heat recovery unit via Bluetooth.

At the bottom of the app screen tap: [BT] [Search for devices] select the detected [Internet Module] Internet Module
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 5 of 14
Download update files

Download all required files — panel firmware, unit firmware and factory configuration snapshot. Start by selecting your control panel.

5a — Control panel firmware

Select the panel model installed at the unit.

Step 5 of 14
5a — iSENSE 5i panel firmware
Select your panel hardware version

The HW version is printed on the panel's rating plate. Download the file and save it to a microSD card (FAT32, max 32 GB).

Step 5 of 14
5a — iSWITCH Ti panel firmware
Download the panel firmware
Step 5 of 14
5b — Unit firmware
Download the unit firmware

Extract the downloaded ZIP file — you need the *.pfi file for the update.

Download firmware
Step 5 of 14
5c — Factory configuration snapshot (1/4)
Unit series

The first two letters of the code on the unit's rating plate.

Know the full model code? Enter it directly, e.g. IT450 S1 AA
Model not found — check the code and try again.
Step 5 of 14
5c — Factory configuration snapshot (2/4)
Unit capacity

The three-digit number after the series code — e.g. IC180, IT450.

Step 5 of 14
5c — Factory configuration snapshot (3/4)
Heat exchanger & control type

E = airENTHALPY  ·  S = airENERGY
1 = iEDGE  ·  4 = iEDGE SMART

Step 5 of 14
5c — Factory configuration snapshot (4/4)
Installation side

Relative to the front of the unit, from the service panel side.

Step 5 of 14
5c — Factory configuration snapshot
Download the configuration snapshot

Extract the downloaded ZIP file — you need the *.json file.

✓ Configuration snapshot found
-
Download configuration snapshot (ZIP)
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 6 of 14
Extract and prepare the downloaded files

Extract the downloaded ZIP files, rename them as needed and save them to your mobile device's storage. Make sure you have:

Files you should have:

1. Unit firmware file — *.pfi
2. Factory configuration snapshot — *.json (extracted from ZIP)
3. Panel firmware file — *.pfc (iSENSE, on microSD card) or *.bin (iSWITCH, in phone storage)
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 7 of 14
Update the control panel
iSENSE 5i
Copy the downloaded *.pfc file to a microSD card (FAT32, max 32 GB). Insert the card into the slot on the bottom of the panel. On the panel screen tap [Panel][Confirm]. Wait for the update to complete, then remove the card.
iSWITCH Ti
In the iCONNECT app tap: [Wrench icon] Wrench password: check code (login required) OK [Find and add update file] select the *.bin file [Start update process] Follow the on-screen instructions.
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 8 of 14
Update the unit firmware
In the iCONNECT app tap: [Ventilation Controller] [Wrench icon] Wrench [Firmware update] password: check code (login required) OK [Find and add update file] select the *.pfi file [Start update process] The process may take several minutes. Leave the device undisturbed.
⏳ Warning
Do not change any unit settings during the update. Wait for the success notification.
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 9 of 14
Restore factory settings
In the iCONNECT app tap: [Ventilation Controller] [Service settings] password: check code (login required) OK at the bottom, grey toggle [Default settings] The grey toggle will turn green. Wait until the green toggle returns to grey — this signals the process is complete. Return to the home screen.
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 10 of 14
Import the factory configuration snapshot
In the iCONNECT app tap: [Ventilation Controller] [Wrench icon] Wrench Configuration snapshots password: check code (login required) OK [Import configuration snapshot] select the downloaded *.json file Follow the on-screen instructions in the app.
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 11 of 14
Load the configuration snapshot
In the iCONNECT app tap: [Ventilation Controller] [Wrench icon] Wrench Configuration snapshots password: check code (login required) OK [Load configuration snapshot] select the imported *.json file Loading takes around 10–15 seconds. Leave the device undisturbed.
⏳ Warning
Do not interrupt the configuration snapshot loading process.
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 12a of 14
Reset filter run-time
Applies to: iEDGE (type E1 / S1)

If your unit uses the iEDGE SMART system (type E4 / S4), skip this step.

In the iCONNECT app tap: [Ventilation Controller] [User settings] [Advanced settings] [Filters] grey toggle [Reset filter run-time] The grey toggle will turn green. Wait until the green toggle returns to grey. Return to the home screen.
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 12b of 14
Calibrate filter operation
Applies to: iEDGE SMART (type E4 / S4)

If your unit uses the iEDGE system (type E1 / S1) — this step does not apply, proceed to the next one.

In the iCONNECT app tap: [Ventilation Controller] [User settings] [Advanced settings] [Filters] grey toggle [Force filter replacement procedure] [Start calibration? YES] OK Follow the on-screen instructions. If a [Calibration Error] message appears — check the filter condition.
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 13 of 14
Calibrate the fan operating range
Applies to: iEDGE SMART (type E4 / S4)

If your unit uses the iEDGE system (type E1 / S1) — this step does not apply, proceed to the next one.

In the iCONNECT app tap: [Ventilation Controller] [Service settings] password: check code (login required) OK [Fan settings] [Constant flow — control calibration] grey toggle [Activate calibration] The grey toggle will turn green. Calibration starts automatically. Wait until the process finishes, then tap [End calibration] and return to the home screen.
⏳ Warning
Resolve all unit faults before calibration. View faults via the ⚠ icon at the bottom of the screen.
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.
Step 14 of 14
Switch the panel back to Wi-Fi and finish

Switch the control panel from Bluetooth mode back to Wi-Fi.

iSWITCH Ti
Press and hold the [on/off] icon on/off until the indicators begin flashing. Slow flashing (once per second) or steady light = Wi-Fi active.
iSENSE 5i
On the home screen tap: User Menu Settings WiFi Mode — switch from BT to WiFi
✓ First start-up complete
All 14 steps completed
The panel, unit and configuration have been updated. The device is ready for operation.
💡 Note
If the app becomes unresponsive at any step — close and reopen the app, then repeat that step.